You need to upgrade your Flash Player or to allow javascript to enable Website menu.
Get Flash Player
Каталог >> Техника автоматизации >> Bihl+Wiedemann >> BWU1650, BW1659, BWU1651, BW1660, BWU1652, BW1661

AS-i 3.0 from Ident. no. 11866 (see lateral Label)

1 AS-i Master, Modbus TCP Slave

 

Recognition of Duplicate AS-i Addresses

 

AS-i Earth Fault Detector integrated

 

AS-i Noise Detector integrated

 

 

 

 

Art. no.

BWU1650

Art. no.

BW1659
Class 1 Div 2 (Group A, B, C & D, T-Code 4)

 

Operating current

Master power supply
approx. 200 mA out of AS-i circuit

Operating voltage

AS-i voltage 30 V DC

Ethernet TCP/IP interface

according to IEEE 802.3, 10BaseT, (RJ-45 connector), Modbus TCP

Baud rates

10/100 MBaud

AS-i cycle time

150 μs*(number of slaves + 2)

Displays

 

LCDs

displaying slave addresses and error messages

LED green (power)

Power on

LED green (ser active)

Ethernet network active

LED red (config error)

configuration error

LED green (U AS-i)

AS-i voltage OK

LED green (AS-i active)

AS-i normal operation active

LED green (prg enable)

automatic address programming enabled

LED yellow (prj mode)

the master is in configuration mode

Buttons

4

Voltage of insulation

≥ 500 V

EMC directions

EN 50 082, EN 50 081

Operating temperature

0°C ... +55°C

Storage temperature

-25°C ... +85°C

Housing

AS-i master housing in stainlees steel

Dimensions (L, W, H)

120 mm, 100 mm, 83 mm

Protection category (DIN 40 050)

IP20

Tolerable loading refering to impacts and vibrations

according to EN 61 131-2

Weight

550 g

Accessories:

  • Software "AS-i Control Tools" with serial cable for AS-i master in stainlees steel (art. no. BW1602)
  • Cross-Link cable (art. no. BW1304)

 

 

 

 

 

 

AS-i 3.0 from Ident. no. 11866 (see lateral Label)

2 AS-i Masters, Modbus TCP Slave

 

Recognition of Duplicate AS-i Addresses

 

AS-i Earth Fault Detector integrated

 

AS-i Noise Detector integrated

 

BWU1651: redundant power supply out of AS-i:
all fundamental functions of the device remain available even in case of
power failure in one of the two AS-i networks

 

BWU1652 and BW1661
in version 1 Power Supply for 2 AS-i circuits:
only 1 Gateway + 1 AS-i Power Supply for 2 AS-i Networks

 

 

Art. no.

BWU1651

 

BWU1652

Art. no.

 

BW1660
Class 1 Div 2
(Group A, B, C & D, T-Code 4)

 

BW1661
Class 1 Div 2
(Group A, B, C & D, T-Code 4)

 

Operating current

Master power supply
approx. 200 mA out of AS-i circuit 1
(approx. 70 mA ... 200 mA)
approx. 200 mA out of AS-i circuit 2
(approx. 70 mA ... 200 mA);
in sum max. 270 mA

approx. 200 mA out of AS-i circuit 1
approx. 70 mA out of AS-i circuit 2

version "1 Power Supply, 1 Gateway for 2 AS-i Circuits", approx. 250 mA (PELV Supply)

Ethernet TCP/IP interface

according to IEEE 802.3, 10BaseT, (RJ-45 connector), Modbus TCP

Baud rates

10/100 MBaud

AS-i cycle time

150 μs*(number of slaves + 2)

Displays

 
LCDs
displaying slave addresses and error messages
LED green (power)
power on
LED green (ser active)
Ethernet network active
LED red (config error)
configuration error
LED green (U AS-i)
AS-i voltage OK
LED green (AS-i active)
AS-i normal operation active
LED green (prg enable)
automatic address programming enabled
LED yellow (prj mode)
the master is in configuration mode

Buttons

4

Voltage of insulation

≥ 500 V

EMC directions

EN 50 082, EN 50 081

Operating temperature

0°C ... +55°C

Storage temperature

-25°C ... +85°C

Housing

AS-i master housing in stainlees steel

Dimensions (L, W, H)

120 mm, 100 mm, 83 mm

Protection category (DIN 40 050)

IP20

Weight

550 g

 

Accessories:

  • Software "AS-i Control Tools" with serial cable for AS-i master in stainlees steel (art. no. BW1602)
  • Cross-Link cable (art. no. BW1304)
  • Power supply 4A (art. no. BW1649)/8A (art. no. BW1593) for art. no. BWU1652

Информация взята с официального сайта компании Bihl+Wiedemann  http://www.bihl-wiedemann.de

 